Add to Cart
Mitsubishi CC-Link Module Analog To Digital V2 A/D Conversion Unit AJ65VBTCU-68ADIN PLC
Product description of Mitsubishi A/D Converter Unit AJ65VBTCU-68ADIN
Station type | Remote device station |
Number of stations occupied | Ver. 1 mode, 3 stations Ver. 2 mode, 1 station |
CC-Link version | Ver.1, Ver.2 |
External dimensions | 115(H)×41(W)×67(D)[mm] |
Mass | 0.17kg |
Features of Mitsubishi A/D Converter Unit AJ65VBTCU-68ADIN
* Compatible with Ver. 2
On the conventional model, three stations occupied eight channels, whereas a single station occupies eight channels on this module.
It can also be used as conventional Ver. 1 depending on the setting of the rotary switch.
* Highly accurate
This input module performs A/D conversion with an accuracy of ±0.3% to the maximum digital output value when the working ambient temperature is between 0℃ and 55℃, or with an accuracy of ±0.2% to the maximum digital output value when the working ambient temperature is 25±5℃.
* The analog input range can be switched for each channel, and input/output conversion characteristics can be changed.
* A high resolution of 1/±4000 is realized.
By switching the input range, the resolution of digital values can be set to either 1/4000 or 1/±4000 (AJ65VBTCU-68ADVN only), providing high-resolution digital values.
* Sampling or averaging can be designated.
Sampling or averaging can be designated for each channel as the conversion method.
Number of analog input points | 4 points (4 channels) | ||
---|---|---|---|
Analog input | Voltage | DC-10 to + 10V (input resistance value: 1MΩ) | |
Current | DC-20 to + 20mA (input resistance value: 250Ω) | ||
Digital output | 0-4000, -2000- + 2000 | ||
Input / output characteristics and resolution | Input range | Digital output value (maximum resolution) | |
Voltage input | -10 to 10V | 0-4000 or -2000-2000 (5mV) | |
0-10V | 0-4000 or -2000-2000 (2.5mV) | ||
0-5V | 0-4000 or -2000-2000 (1.25mV) | ||
1-5V | 0-4000 or -2000-2000 (1.0 mV) | ||
Current input | -20 to 20mA | 0-4000 or -2000-2000 (20 μA) | |
0-20mA | 0-4000 or -2000-2000 (10μA / 5μA) | ||
4-20mA | 0-4000 or -2000-2000 (4 μA) | ||
Accuracy (accuracy with respect to the maximum value of digital output value) | Ambient temperature: 0-55 ° C | ± 1% | |
A / D conversion speed | 1ms / channel | ||
Absolute maximum input | Voltage | ± 15V | |
Current | ± 30mA | ||
Insulation method | Power supply / communication system and analog input: Photocoupler isolated channel: Non-insulated | ||
Dielectric strength | Between power supply / communication system batch and analog input batch: AC500V 1 minute | ||
Insulation resistance | Between power supply / communication system batch and analog input batch: DC500V insulation resistance tester 10MΩ or more | ||
Station type | Remote device station (Ver.1 remote device station) | ||
Number of occupied stations | 2 stations | ||
Unit power supply | Voltage | DC24V (DC18-30V) | |
Current | 0.12A (at 24V DC) | ||
External wiring connection method | Communication unit, unit power supply unit: 7-point 2-piece terminal block (M3.5 screw) Input / output unit: 27-point 2-piece terminal block (M3.5 screw) | ||
External dimensions | Height (H) | 65mm | |
Width (W) | 151.9mm | ||
Depth (D) | 63mm | ||
mass | 0.35kg |
Number of analog input points | 4 points (4 channels) | ||
---|---|---|---|
Analog input | Voltage | DC-10 to + 10V (input resistance value: 1MΩ) | |
Current | DC0 to 20mA (input resistance value: 250Ω) | ||
Digital output | -4096 to +4095 | ||
Input / output characteristics and resolution | Input range | Digital output value (maximum resolution) | |
Voltage input | -10 to 10V | -4000-4000 (2.5mV) | |
User range setting 1 (-10 to 10V) | -4000-4000 (2.5mV) | ||
0-5V | 0-4000 (1.25mV) | ||
1-5V | 0-4000 (1.0 mV) | ||
User range setting 2 (0 to 5V) | 0-4000 (1.0 mV) | ||
Current input | 0-20mA | 0-4000 (5 μA) | |
4-20mA | 0-4000 (4μA) | ||
User range setting (0 to 20mA) | 0-4000 (4μA) | ||
Accuracy (accuracy with respect to the maximum value of digital output value) | Ambient temperature: 25 ± 5 ° C | ± 0.2% | |
Ambient temperature: 0-55 ° C | ± 0.4% | ||
A / D conversion speed | 1ms / channel | ||
Absolute maximum input | Voltage | ± 15V | |
Current | ± 30mA | ||
Insulation method | Communication system and analog input batch: Photocoupler isolated Power supply system and analog input batch: Photocoupler isolated Channel: Non-insulated | ||
Dielectric strength | Between power supply / communication system batch and analog input batch: AC500V 1 minute | ||
Station type | Remote device station (Ver.1 remote device station) | ||
Number of occupied stations | 1 station | ||
Unit power supply | Voltage | DC24V (DC20.4-26.4V) | |
Current | 0.090A (at 24V DC) | ||
Inrush current | 8.5A, 2.3ms or less | ||
External wiring connection method | Communication unit, unit power supply unit: 7-point 2-piece terminal block (M3 screw) Input / output unit: 18-point direct mounting terminal block (M3 screw) | ||
External dimensions | Height (H) | 50mm | |
Width (W) | 118mm | ||
Depth (D) | 40mm | ||
mass | 0.20kg |
Number of analog input points | 8 points (8 channels) | ||
---|---|---|---|
Analog input | Voltage | DC0 to 20mA (input resistance value: 250Ω) | |
Digital output | -96 ~ + 4095 | ||
Input / output characteristics and resolution | Input range | Digital output value (maximum resolution) | |
Current input | 0-20mA | 0-4000 (5 μA) | |
4-20mA | 0-4000 (4μA) | ||
User range setting (0 to 20mA) | 0-4000 (4μA) | ||
Accuracy (accuracy with respect to the maximum value of digital output value) | Ambient temperature: 25 ± 5 ° C | ± 0.3% | |
Ambient temperature: 0-55 ° C | ± 0.2% | ||
A / D conversion speed | 1ms / channel | ||
Absolute maximum input | Current | ± 30mA | |
Insulation method | Communication system and analog input batch: Photocoupler isolated Power supply system and analog input batch: Transformer isolated channel: Non-insulated | ||
Dielectric strength | Between power supply / communication system batch and analog input batch: AC500V 1 minute | ||
Protection grade | IP1XB | ||
Station type | Remote device station (Ver.1 remote device station or Ver.2 remote device station) | ||
Number of occupied stations | Ver.1 Remote device station: 3 stations Ver.2 Remote device station: 1 station (extended cyclic setting: 4 times) | ||
communication cable | Ver.1.10 compatible CC-Link dedicated cable: FANC-110SBH, FA-CBL200PSBH, CS-110 | ||
Unit power supply | Voltage | DC24V (DC20.4-26.4V, ripple rate within 5%) | |
Current | 0.10A (at 24V DC) | ||
Inrush current | 4.2A, 1.2ms or less | ||
External wiring connection method | Communication unit: One-touch connector for communication (sold separately) Unit power supply unit: One-touch connector for power supply / FG (sold separately) Input / output unit: One-touch connector for I / O (sold separately) | ||
External dimensions | Height (H) | 115mm | |
Width (W) | 41mm | ||
Depth (D) | 67mm | ||
mass | 0.17kg |
Number of analog input points | 8 points (8 channels) | ||
---|---|---|---|
Analog input | Voltage | DC-10 to + 10V (input resistance value: 1MΩ) | |
Digital output | -4096 to +4095 | ||
Input / output characteristics and resolution | Input range | Digital output value (maximum resolution) | |
Voltage input | -10 to 10V | -4000-4000 (2.5mV) | |
User range setting 1 (-10 to 10V) | -4000-4000 (2.5mV) | ||
0-5V | 0-4000 (1.25mV) | ||
1-5V | 0-4000 (1.0 mV) | ||
User range setting 2 (0 to 5V) | 0-4000 (1.0 mV) | ||
Accuracy (accuracy with respect to the maximum value of digital output value) | Ambient temperature: 25 ± 5 ° C | ± 0.3% | |
Ambient temperature: 0-55 ° C | ± 0.2% | ||
A / D conversion speed | 1ms / channel | ||
Absolute maximum input | Voltage | ± 15V | |
Insulation method | Communication system and analog input batch: Photocoupler isolated Power supply system and analog input batch: Transformer isolated channel: Non-insulated | ||
Dielectric strength | Between power supply / communication system batch and analog input batch: AC500V 1 minute | ||
Protection grade | IP1XB | ||
Station type | Remote device station (Ver.1 remote device station or Ver.2 remote device station) | ||
Number of occupied stations | Ver.1 Remote device station: 3 stations Ver.2 Remote device station: 1 station (extended cyclic setting: 4 times) | ||
communication cable | Ver.1.10 compatible CC-Link dedicated cable: FANC-110SBH, FA-CBL200PSBH, CS-110 | ||
Unit power supply | Voltage | DC24V (DC20.4-26.4V, ripple rate within 5%) | |
Current | 0.10A (at 24V DC) | ||
Inrush current | 4.2A, 1.2ms or less | ||
External wiring connection method | Communication unit: One-touch connector for communication (sold separately) Unit power supply unit: One-touch connector for power supply / FG (sold separately) Input / output unit: One-touch connector for I / O (sold separately) | ||
External dimensions | Height (H) | 115mm | |
Width (W) | 41mm | ||
Depth (D) | 67mm | ||
mass | 0.17kg |