Ask Latest Price
Video Channel
Place of Origin :China/Japan
Brand Name :Mitsubishi
Model Number :FX3U-3A-ADP
Packaging Details :Carton packaging
Supply Ability :10pc/per week
Price :$50-$500
MOQ :1/pc
Port :Shenzhen & Guanzhou /Selectable
Payment Terms :T/T, western union
Contact Now

Add to Cart

Find Similar Videos
View Product Description

High Quality Mitsubishi PLC FX3U-3A-ADP

High Quality Mitsubishi PLC FX3U-3A-ADP

A high-precision analog input / output adapter with a resolution of 12-bit binary.
[Features]
-Two-channel input (voltage: DC0 to 10V or current: DC4 to 20mA) and one-channel output (voltage: DC0 to 10V or current: DC4 to 20mA) are possible.
-Input is for each channel. Voltage or current input can be specified.
-Data can be transferred without a program (without a dedicated instruction).
[Application]
-Convenient for converting analog input signals to digital values ​​and digital values ​​to analog output signals.

Conformity standard

Conformity standard UL / cUL KC

Product Specifications

Analog input Analog input range Voltage input DC0-10V (input resistance 198.7kΩ)
Current input DC4-20mA (input resistance 250Ω)
Number of input channels 2 channels
Absolute maximum input Voltage input -0.5V, + 15V
Current input -2mA, + 30mA
Input characteristics The input mode (voltage / current input) can be set for each channel.
Digital output 12bit binary
resolution Voltage input 2.5mV (10V x 1/4000)
Current input 5μA (16mA x 1/3200)
Comprehensive accuracy Voltage input Ambient temperature 25 ° C ± 5 ° C: ± 0.5% (± 50mV) for full scale 10V
Ambient temperature 0 ° C to 55 ° C: ± 1.0% (± 100mV) for full scale 10V
Current input Ambient temperature 25 ° C ± 5 ° C: ± 0.5% (± 80μA)
for full scale 16mA Ambient temperature 0 ° C to 55 ° C: ± 1.0% (± 160μA) for full scale 16mA
A / D conversion time When connecting FX3U / FX3UC sequencer 80 μs x number of input channels used + 40 μs x number of output channels used (data is updated every calculation cycle)
When connecting FX3S / FX3G / FX3GC sequencer 90 μs x number of input channels used + 50 μs x number of output channels used (data is updated every calculation cycle)
Insulation method ・ Insulation between analog input / output section and sequencer by photocoupler
・ Insulation between drive power supply and analog input / output section by DC / DC converter
・ Non-insulation between each channel
Analog output Analog output range Voltage output DC0-10V (external load resistance 5k-1MΩ)
Current output DC4 to 20mA (external load resistance 500Ω or less)
Number of output channels 1 channel
Output characteristics The output mode (voltage / current output) can be set.
Digital input 12bit binary
resolution Voltage output 2.5mV (10V x 1/4000)
Current output 4μA (16mA x 1/4000)
Comprehensive accuracy Voltage output Ambient temperature 25 ° C ± 5 ° C: ± 0.5% (± 50mV) for full scale 10V
Ambient temperature 0 ° C to 55 ° C: ± 1.0% (± 100mV) for full scale 10V
External load resistance (Rs) is less than 5kΩ In that case, the following calculation will be increased.
(Increases by 100 mV per 1%.)
47 × 100 / (Rs + 47) -0.9 (%)
Current output Ambient temperature 25 ° C ± 5 ° C: ± 0.5% (± 80μA)
for full scale 16mA Ambient temperature 0 ° C to 55 ° C: ± 1.0% (± 160μA) for full scale 16mA
D / A conversion time When connecting FX3U / FX3UC sequencer 80 μs x number of input channels used + 40 μs x number of output channels used (data is updated every calculation cycle)
When connecting FX3S / FX3G / FX3GC sequencer 90 μs x number of input channels used + 50 μs x number of output channels used (data is updated every calculation cycle)
Insulation method ・ Insulation between analog input / output section and sequencer by photocoupler
・ Insulation between drive power supply and analog input / output section by DC / DC converter
・ Non-insulation between each channel
Number of I / O occupied points 0 points (not related to the maximum number of I / O points in the sequencer)
Applicable sequencer FX3S, FX3G (Ver.1.20 or later), FX3U (Ver.2.61 or later), FX3GC, FX3UC (Ver.2.61 or later)
FX3S-CNV-ADP is required to connect to FX3S.
FX3G-CNV-ADP is required to connect to FX3G.
An expansion board is required to connect to FX3U and FX3UC-32MT-LT (-2).
mass About 0.1kg

Product Specifications

power supply Conversion circuit drive power supply DC24V + 20% -15%
Connect a DC24V power supply to the 90mA terminal block and supply it.
Interface drive power supply DC5V 20mA
Internal power is supplied from the DC5V power supply of the basic unit.

Product Specifications

Ambient temperature 0-55 ℃ ・ ・ ・ ・ ・ During operation -25 ~ 75 ℃ ・ ・ ・ ・ ・ During storage
Relative humidity 5 to 95% RH (no condensation) ・ ・ ・ ・ ・ ・ During operation
Vibration resistant When mounting the DIN rail Frequency: 10-57Hz One-sided amplitude: 0.035mm X, Y, Z 10 times in each direction (80 minutes in total)
Frequency: 57-150Hz Acceleration: 4.9m / s 2 X, Y, Z 10 times in each direction (80 minutes in total)
At the time of direct mounting Frequency: 10-57Hz One-sided amplitude: 0.075mm X, Y, Z 10 times in each direction (80 minutes in total)
Frequency: 57-150Hz Acceleration: 9.8m / s 2 X, Y, Z 10 times in each direction (80 minutes in total)
Impact resistance 147m / s 2 , action time 11ms, sine and cosine half-wave pulse 3 times in each direction of X, Y, Z
Noise resistance Based on a noise simulator with a noise voltage of 1,000 Vp-p, a noise width of 1 μs, a rise of 1 ns, and a period of 30 to 100 Hz.
Withstand voltage Between all terminals and ground terminal: AC500V 1 minute
Insulation resistance Between all terminals and ground terminal: 5MΩ or more with DC500V insulation resistance tester
ground Class D grounding (grounding resistance: 100Ω or less) <Common grounding with strong electrical system is not possible>
Grounding should be dedicated grounding or shared grounding.
Atmosphere of use No corrosive or flammable gas, no terrible conductive dust
Altitude used
It cannot be used in an environment where the pressure is 2000 m or less and the atmospheric pressure is higher than the atmospheric pressure. It may break down.