Add to Cart
Item | AC power supply | DC power supply | |
---|---|---|---|
Model | CP2E-[][][]D[]-A | CP2E-[][][]D[]-D | |
Enclosure | Mounted in a panel | ||
Dimensions (H × D × W) | CPU Unit with 14 or 20 I/O points (CP2E-[]14/20D[]-[]): 90mm *1 ×80mm *2 × 86mm CPU Unit with 30 I/O points (CP2E-[]30D[]-[]): 90mm *1 × 80mm *2 × 130mm CPU Unit with 40 I/O points (CP2E-[]40D[]-[]): 90mm *1 × 80mm *2 × 150mm CPU Unit with 60 I/O points (CP2E-[]60D[]-[]): 90mm *1 × 80mm *2 × 195mm | ||
Weight | CPU Unit with 14 I/O points (CP2E-[]14D[]-[]): 335g max. CPU Unit with 20 I/O points (CP2E-[]20D[]-[]): 340g max. CPU Unit with 30 I/O points (CP2E-[]30D[]-[]): 580g max. CPU Unit with 40 I/O points (CP2E-[]40D[]-[]): 640g max. CPU Unit with 60 I/O points (CP2E-[]60D[]-[]): 780g max. | ||
Electrical specifications | Supply voltage | 100 to 240 VAC 50/60 Hz | 24 VDC |
Operating voltage range | 85 to 264 VAC | 20.4 to 26.4 VDC | |
Power consumption | 15 VA/100 VAC max. 25 VA/240 VAC max. (CP2E-[]14/20D[]-A) | 13W max. (CP2E-[]14/20D[]-D) | |
50 VA/100 VAC max. 70 VA/240 VAC max. (CP2E-[]30/40/60D[]-A) | 20W max. (CP2E-[]30/40/60D[]-D) *4 | ||
Inrush current | 120 VAC, 20 A for 8 ms max. for cold start at room temperature 240 VAC, 40 A for 8 ms max. for cold start at room temperature | 24 VDC, 30A for 20 ms max. for cold start at room temperature | |
External power supply *3 | Not provided. (CP2E-[]14/20D[]-A) 24 VDC, 300 mA (CP2E-[]30/40/ 60D[]-A) | Not provided. | |
Insulation resistance | 20 MΩ min. (at 500 VDC) between the external AC terminals and GR terminals | Not csolated between primary and secondary DC power supplies | |
Dielectric strength | 2,300 VAC 50/60Hz for 1 min between AC external and GR terminals Leakage current: 5 mA max. | Not csolated between primary and secondary DC power supplies | |
Power interrupt time | 10 ms min. | 2 ms min. | |
Application environment | Ambient operating temperature | -20 to 60°C | |
Ambient humidity | 10% to 90% | ||
Atmosphere | No corrosive gas. | ||
Ambient storage temperature | -20 to 75°C (excluding battery) | ||
Altitude | 2,000 m max. | ||
Pollution degree | 2 or less: Conforms to IEC61010-2-201. | ||
Noise resistance | 2 kV on power supply line (Conforms to IEC61000-4-4.) | ||
Overvoltage category | Category II: Conforms to IEC61010-2-201. | ||
EMC immunity level | Zone B | ||
Vibration resistance | Conforms to IEC60068-2-6. 5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz Acceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total) | ||
Shock resistance | Conforms to IEC60068-2-27. 147 m/s2, 3 times in X, Y, and Z directions | ||
Terminal block | Fixed (not removable) | ||
Terminal screw size | M3 | ||
Applicable standards | Conforms to EC Directives, KC, UL and EAC. | ||
Grounding method | Ground to 100Ω or less. |